ADCP-80-570Issue 2March 20061361499 Rev APowerWorx® Power Distribution ProductsCircuit Breaker Panel With Reset Switch User Manual20629-A
ADCP-80-570 • Issue 2 • March 2006Page 4© 2006, ADC Telecommunications, Inc.• Rear protective input terminal covers (2) and output/alarm terminal cove
ADCP-80-570 • Issue 2 • March 2006Page 5© 2006, ADC Telecommunications, Inc.Each of the power buses supports seven circuit breaker positions including
ADCP-80-570 • Issue 2 • March 2006Page 6© 2006, ADC Telecommunications, Inc.The individual terminals are on 0.375 inch (9.525 mm) centers with a dista
ADCP-80-570 • Issue 2 • March 2006Page 7© 2006, ADC Telecommunications, Inc.1.12 Breaker Alarm IndicatorsFor each bus, the circuit breaker panel has o
ADCP-80-570 • Issue 2 • March 2006Page 8© 2006, ADC Telecommunications, Inc.The card should be filled out with circuit information for each of the cir
ADCP-80-570 • Issue 2 • March 2006Page 9© 2006, ADC Telecommunications, Inc.1.20 Protective CoversThe panel has three protective covers mounted on the
ADCP-80-570 • Issue 2 • March 2006Page 10© 2006, ADC Telecommunications, Inc.1.22 SpecificationsTable 2 lists specifications for the circuit breaker p
ADCP-80-570 • Issue 2 • March 2006Page 11© 2006, ADC Telecommunications, Inc.1.23 DimensionsDimens io nsFigure 6. Panel DimensionsTorqueMounting brack
ADCP-80-570 • Issue 2 • March 2006Page 12© 2006, ADC Telecommunications, Inc.2 ACCESSORIESThe following accessories for the PowerWorx circuit breaker
ADCP-80-570 • Issue 2 • March 2006Page 13© 2006, ADC Telecommunications, Inc.4.1 Installation Tools RequiredThe following tools are required to instal
ADCP-80-570 • Issue 2 • March 2006 • PrefacePage iiCOPYRIGHT© 2006, ADC Telecommunications, Inc.All Rights ReservedPrinted in the U.S.A.REVISION HISTO
ADCP-80-570 • Issue 2 • March 2006Page 14© 2006, ADC Telecommunications, Inc.Test 1: Input Battery to Input Return—Use the following procedure:1. Conn
ADCP-80-570 • Issue 2 • March 2006Page 15© 2006, ADC Telecommunications, Inc.Test 3: Input Return to Output Return—Use the following procedure:1. Star
ADCP-80-570 • Issue 2 • March 2006Page 16© 2006, ADC Telecommunications, Inc.4.4 Cable Management Bar (Optional Accessory)Before installing the circui
ADCP-80-570 • Issue 2 • March 2006Page 17© 2006, ADC Telecommunications, Inc.Use the following procedure to install the circuit breaker panel in the r
ADCP-80-570 • Issue 2 • March 2006Page 18© 2006, ADC Telecommunications, Inc.Figure 13. Mounting Panel on Rack4.6 Installing Designation CardsAttach t
ADCP-80-570 • Issue 2 • March 2006Page 19© 2006, ADC Telecommunications, Inc.• Chassis ground conductor: Use two #10 AWG wires if using both chassis g
ADCP-80-570 • Issue 2 • March 2006Page 20© 2006, ADC Telecommunications, Inc.5. If connecting bare wire, wrap the bare wire around the contact in a cl
ADCP-80-570 • Issue 2 • March 2006Page 21© 2006, ADC Telecommunications, Inc.3. Terminate the wires at the screw-down barrier strip as follows (Figure
ADCP-80-570 • Issue 2 • March 2006Page 22© 2006, ADC Telecommunications, Inc. Use the following procedure to connect input power wires (Figure 17):1.
ADCP-80-570 • Issue 2 • March 2006Page 23© 2006, ADC Telecommunications, Inc.6. Use a heat gun to apply heat to the heat shrink insulation until it ti
ADCP-80-570 • Issue 2 • March 2006 • PrefacePage iii© 2006, ADC Telecommunications, Inc.TABLE OF CONTENTSContent PageAbout This Manual . . . . . . .
ADCP-80-570 • Issue 2 • March 2006Page 24© 2006, ADC Telecommunications, Inc.5 TESTINGThis section describes how to test the circuit breaker panel aft
ADCP-80-570 • Issue 2 • March 2006Page 25© 2006, ADC Telecommunications, Inc.6 OPERATIONThis section describes how to operate the circuit breaker pane
ADCP-80-570 • Issue 2 • March 2006Page 26© 2006, ADC Telecommunications, Inc.6.2 Using the Reset SwitchThe purpose of the Reset switch is to allow you
ADCP-80-570 • Issue 2 • March 2006Page 27© 2006, ADC Telecommunications, Inc.3. Insert a flat-bladed screwdriver into the slot above the circuit break
ADCP-80-570 • Issue 2 • March 2006Page 28© 2006, ADC Telecommunications, Inc.9. Disconnect the power and load wires (#14 AWG white and black wires) an
ADCP-80-570 • Issue 2 • March 2006Page 29© 2006, ADC Telecommunications, Inc.8 CUSTOMER INFORMATION AND ASSISTANCE© 2006, ADC Telecommunications, Inc.
ADCP-80-570 • Issue 2 • March 2006Page 30© 2006, ADC Telecommunications, Inc.
ADCP-80-570 • Issue 2 • March 2006Page 31© 2006, ADC Telecommunications, Inc.APPENDIX A: ALLOWABLE AMPACITIES OF INSULATED CONDUCTORSThis appendix pro
ADCP-80-570 • Issue 2 • March 2006Page 32© 2006, ADC Telecommunications, Inc.* Unless otherwise specifically permitted in the code, as defined in the
ADCP-80-570 • Issue 2 • March 2006 • PrefacePage iv© 2006, ADC Telecommunications, Inc.TABLE OF CONTENTSContent Page4.10 Connecting Output. . . . . .
iwww.adc.com
ADCP-80-570 • Issue 2 • March 2006 • PrefacePage v© 2006, ADC Telecommunications, Inc.ABOUT THIS MANUALThis manual describes the PowerWorx Circuit Bre
ADCP-80-570 • Issue 2 • March 2006 • PrefacePage vi© 2006, ADC Telecommunications, Inc.LIST OF ACRONYMSLED -- Light-Emitting DiodeWarning: To prevent
ADCP-80-570 • Issue 2 • March 2006Page 1© 2006, ADC Telecommunications, Inc.1 PRODUCT DESCRIPTIONThis section describes the PowerWorx Circuit Breaker
ADCP-80-570 • Issue 2 • March 2006Page 2© 2006, ADC Telecommunications, Inc.Figure 1. Circuit Breaker Panel ComponentsBUS APOWER-ONINDICATOR(GREEN LED
ADCP-80-570 • Issue 2 • March 2006Page 3© 2006, ADC Telecommunications, Inc.1.3 Packaged HardwareThe shipped product includes hardware components that