DETAIL ENGINEERING REQUIREMENTS Section 9, ATT-TP-76400
AT&T January, 2012
B.) STS1 shall be Yellow, except for Southeast region.
5.6.15 DSX-3 Rear Cross Connect bays/line-ups shall require rear aisle lighting to meet with the
minimum foot candle requirement for Equipment Frame Area Maintenance Aisle standards as
described in Table 6-3 of Section 6 in ATT-TP-76400.
5.7 DSX Cross-Connect References
ATT-002-316-041, DSX-1 Deployment Standards
ATT-002-316-042, DSX-3 Deployment Standards
ATT-E-01115-W AT&T-Interconnect Drawings (DSX-3) FX
ATT-E-01115-E AT&T-Equipment Drawings (DSX-3) FX
ATT-E-01175-E AT&T-Equipment Drawings (DSX-1) RX
ATT-E-01175-W AT&T-Interconnect Drawings (DSX1) RX
ATT-E-01117-W AT&T-Interconnect Drawing DSX-3 RX
ATT-E-01117-E AT&T-Equipment Drawing DSX-3 RX
ATT-E-01150-E AT&T-Drawings BOR-SWBT version DS3/STS-1 IOR/BOR
ATT-E-01150-W AT&T-Drawings BOR-SWBT version DS3/STS-1 IOR/BOR
ATT-E-01101-E AT&T-Equipment Drawings DS1-IOR
ATT-E-01101-W AT&T-Interconnect Drawings DS1-IOR
6. FIBER DISTRIBUTING FRAMES (FDF)
6.1. General
6.1.1 A FDF architecture shall serve as the primary interface between outside plant (OSP) fiber
optic facilities entering and leaving a building and the fiber optic equipment installed within a
building.
6.1.2 In smaller legacy POPS (a pre-existing facility typically less than 2000 square feet) fiber may
be run directly from the splitter shelf to the NE.
6.1.3 The FDF shall provide a centralized point for the organization and administration of the fiber
optic facility and intra-building equipment cables, providing a flexible platform for future fiber
growth, and providing re-arrangeable connections between any two terminations or
appearances.
6.1.4 FDF systems are suitable for use in both large and small offices, digital loop carriers,
controlled environmental vaults (CEVs), POP’s and customer premises.
9-13