ADCP-80-545 • Issue 3 • March 2006
Page 9
© 2006, ADC Telecommunications, Inc.
Environmental
Operating temperature –5º C to +55º C
Storage temperature –45º C to +85º C
Humidity range 0% to 95% humidity No condensation
Altitude range Up to 13,000 ft. (3.96 km)
Fire rating All components UL94-V1 or
better
Acoustic noise 0 dBA above ambient
Heat dissipation (fully loaded) 160 watts max. at 200 Amps 80 watts per bus
Torque
Mounting bracket chassis screws 15 pound force-inches 1.7 Newton meters
Mounting bracket rack screws 27 pound force-inches 3.1 Newton meters
Input power terminal nuts 32 pound force-inches 3.6 Newton meters
Output power terminal screws 15 pound force-inches 1.7 Newton meters
Alarm terminal screws 8 pound force-inches 0.9 Newton meters
Grounding stud nuts 23 pound force-inches 2.6 Newton meters
Table 2. Circuit Breaker Panel Specifications, continued
PARAMETER SPECIFICATION REMARKS