General Information
10
Quick Selection Table For Relays
Bulletin No.
700-HG 700-HHF 700-HJ
Type
Power Relay Power Relay Magnetic Latching Relay
Features
Panel Mount with Screw Terminals, Optional
Magnetic Blowouts for Switching DC Loads,
Optional Snap Action Switch
Flange Mounted, Optional LED
Socket Mounted, Ideal for
Lighting Applications
Contact Ratings
Contact
Form
SPST-N.O.-DM, SPDT,
DPST-N.O., DPDT
SPST-NO-DM, DPDT, 3PDT SPDT, DPDT (Single or Dual Coil)
Contact Type
Single Single Single
Contact
Material
AgCdO AgCdO AgCdO
Max. operating
current under
resistive load
30 A 20 A (3PDT), 25 A (DPDT), 30 A (SPDT) 10 A
Min.
permissible
load
10V 50 mA
10V 50 mA
10V 100 mA (3PDT)
10V 50 mA
Coil Ratings
Coil Voltage
AC:
24V, 120V, 240V, 277V, 480V
DC:
12V, 24V, 48V, 110V, 220V, 250V
AC:
24V, 120V, 240V
DC:
6V,12V, 24V
AC:
24V, 120V, 240V
DC:
12V, 24V,
Permissible
Coil Voltage
Variation
85…110% of Nominal Voltage at 50 Hz
85…110% of Nominal Voltage at 60 Hz
80…110% of Nominal Voltage at DC
85…110% of Nominal Voltage at 50 Hz
85…110% of Nominal Voltage at 60 Hz
80…110% of Nominal Voltage at DC
85…110% of Nominal Voltage at 50 Hz
85…110% of Nominal Voltage at 60 Hz
80…110% of Nominal Voltage at DC
Electrical Ratings
Dielectric
Withstand
Voltage
Pole-to-Pole: 2200V AC
Contact to Coil: 2200V AC
Contact to Frame: 2200V AC
Pole-to-Pole: 2200V AC
Contact to Coil: 2200V AC
Contact to Frame: 1600V AC
Pole-to-Pole: 1500V AC
Contact to Coil: 1500V AC
Contact to Frame: 1500V AC
Electric
Service Life
(cycles)
100,000 minimum 100,000 minimum 100,000 minimum
Reference
Certifications
CE, UL, CSA CE, UR, CSA CE, UR, CSA
Socket
Cat. No(s).
——
700-HN153
700-HN154
Page Number
111 114 94