Bulletin 700-HX
Plug-in Timing Relays
168
Specifications, Continued
➊
700-HX User Manual, pub. number 700-UM002A-EN-D, available at: http://www.theautomationbookstore.com.
➋
An attached waterproof packing is necessary to ensure IP66 waterproofing between the 700-HX and installation pan.
Characteristics
➊
Insulation resistance 100 M
Ω
min. (at 500V DC)
Dielectric strength
2000V AC, 50/60Hz for 1 min. between current-carrying terminals and non-current-carrying
metal parts
(1000V AC for 24V AC/12 to 24V DC type),
1000 VAC, 50/60 Hz for 1 min. between non-continuous contacts
Noise immunity
'+-1.5 kV (between power terminals) for 100 to 240 VAC, +-480V for 24VAC/12 to 24VDC, and
+-600V (between input terminals), square-wave noise by noise simulator (pulse width: 100 ns/1
µ
s, 1-ns rise)
Static immunity
±
8 kV (malfunction),
±
15 kV (destruction)
Vibration resistance Malfunction 10…55 Hz with 0.35 mm single amplitude each in three directions for 10 min.
Shock resistance Malfunction
98 m/s
2
(approx. 10 G) each in three directions
Life expectancy
Mechanical 10 million operations min.
Electrical 100,000 operations min. (5 A at 250V AC, resistive load)
EMC
(EMI) EN61326
Emission Enclosure: EN55011 Group1 class A
Emission AC mains: EN55011 Group1 class A
(EMS) EN61326
Immunity ESD: EN61000-4-2: 4 kV contact discharge (level2)
8 kV air discharge (level3)
Immunity RF-interference: EN61000-4-3: 10 V/m
Approved standards
UL508, CSA C22.2 No.14
Conforms to EN61010-1/IEC61010-1 (Pollution degree 2/overvoltage category II)
Conforms to VDE0106/P 100 (Finger Protection), conforms to NEMA output rating (N/F)
Enclosure ratings Panel surface:IP66 and NEMA Type 4 (indoors)
➋
Weight Approx. 100 g
Certifications CE Certified; UL508; CSA, C22.2 No. 14; ACA
Standards EN61010-1; IEC61010-1; VDE0106/P 100; NEMA 4/ IP66